Dip-Sag Voltage Compensator (DVC)

OKY LTD is trying to take a step further in realizing customer satisfaction

UDS

UD2-1000 is designed to perform the advantages of DVC and UPS in combination.

When an abnormality such as an instantaneous power failure or sag occurs,
it responds to an instantaneous power failure or an instantaneous voltage
drop for 1sec~1.5sec using the fast transfer time (transferred within 2ms),
which is the advantage of DVC. With the long compensation time, the advantage
of UPS, UD2 compensates for about 8 minutes based on 330W load so that
normal equipment operation is available or operation of the operating equipment
can be appropriately stop.

SPECIFICATION

UD2-1000 specification
General Operating Temperature 0℃ ~ 40℃
Operating humidity 10% ~ 90% No water on the surface
Cooling system natural air
Operation type Line Interactive
Input phase two-wire single-phase
Rated voltage 220VAC ± 20% available with other voltages
Rated frequency 60Hz ± 5% available with 50Hz
Total allowable harmonic distortion 15%
Output Output rated capacity 1kVA 700W
Inverter mode Constant accuracy rated voltage ± 2%.
Accuracy of rated frequency Rated frequency ± 1%
Compensation Time(UPS) 8 minutes(based on 50% linear load) same as the UPS compensation time
Compensation time (DVC) 1 second (based on 100% linear load)
Total harmonic distortion within 5% (100% linear load)
Inverter efficiency ≥70% (100% linear load) UPS + DVC
Normal mode output voltage Input voltage ± 2%
Frequency input frequency ± 5%
Efficiency More than 92% efficiency (100% linear load)
Switching Time (Inverter Mode
⇔ Line Mode)
UPS: within 10ms/ DVC: within 2ms same as the DVC transfer time
외형 External size 364mm x 427mm x 713mm (W x D x H) with eyebolt(H : 746.6mm)
Weight 65kgs ± 5%